Description
The MBX boiler water injector makes it possible to keep the boiler running, independently of external energy sources, meeting the requirements of regulatory standard NR-13, item 13.4.1.3, paragraph "c", as an independent water supply system for non-atomized solid fuel boilers or suspended combustion.
Advantages and Benefits
- Own production;
- Technical assistance;
- 100% replacement of parts;
- Personalized service;
- Quality guaranteed;
- Best price.
Technical data
- Water injector for boiler;
- Manual operation;
- It has pressure safety valves;
- Uses steam from the boiler itself;
- Operating range (2.8 kgf/cm² to 9 kgf/cm²);
- Flow rate from 1,400 to 14,900 l/h;
- Connections: Soldering tip;
- Adjustment rod with aluminum handle;
- Nominal diameter 1”, 1.1/2”. 2”.
Normal Gauge | Feed Flow - liters/hour | ||||
---|---|---|---|---|---|
2.8 kgf/cm |
4.2 kgf/cm |
5.6 kgf/cm |
7 kgf/cm |
9 kgf/cm |
|
¾" | 600 | 730 | 950 | 1200 | 1400 |
1" | 1400 | 1750 | 2100 | 2350 | 2600 |
1.½" | 4000 | 5100 | 6100 | 7400 | 8000 |
2" | 8200 | 9400 | 11000 | 13300 | 14900 |
Installation suggestion
Injectors are a mechanism for feeding water into boilers. They use the process' own steam to inject water through the Venturi system. 100% of the parts are tested with warranty, manual and quality certificate. They are produced in Brazil and MBX offers technical assistance and spare parts.